Infrared
Radiant Heating for Commercial / Industrial Applications
|
-
Special
Honeycomb Design Tile for Increased Radiant Output
-
Inputs from 30,000 to 160,000 Btu/hr
-
Suitable for Angle Mount up to 35°
-
All Heaters are Equipped with 100% Gas Shut-Off Safety Control
-
Corrosion-Resistant, Aluminized Steel Body Construction
-
Highly Efficient Aluminum Reflectors
-
Optional Reverberatory Screen
-
Heaters can be Shipped by UPS
|
|
MODEL
|
GAS
TYPE |
INPUT
BTU/HR
|
NO.
OF
BURNERS |
DIMENSIONS
(inches) |
MINIMUM
MOUNTING HEIGHT (feet) |
LENGTH
|
WIDTH
|
HEIGHT
|
DK30
|
Natural
|
30,000
|
1
|
25.75
|
15.75
|
8.25
|
11
|
DK35
|
Natural
|
35,000
|
1
|
25.75 |
15.75
|
8.25
|
12
|
DK40
|
Natural
|
40,000
|
1
|
25.75 |
15.75
|
8.25
|
12
|
DK60
|
Natural
|
60,000
|
2
|
25.75 |
21.75
|
8.25
|
13
|
DK70
|
Natural
|
70,000
|
2
|
25.75 |
21.75
|
8.25
|
13
|
DK80
|
Natural
|
80,000
|
2
|
25.75 |
21.75
|
8.25
|
14
|
DK100
|
Natural
|
100,000
|
3
|
25.75
|
25.75
|
8.25
|
15
|
DK120
|
Natural
|
120,000
|
3
|
25.75
|
25.75
|
8.25
|
16
|
DK140
|
Natural
|
140,000
|
4
|
25.75
|
34
|
8.25
|
17
|
DK160
|
Natural
|
160,000
|
4
|
25.75
|
34
|
8.25
|
18
|
DK33
|
Propane
|
33,000
|
1
|
25.75
|
15.75
|
8.25
|
12
|
DK66
|
Propane
|
66,000
|
2
|
25.75
|
21.75
|
8.25
|
13
|
DK100
|
Propane
|
99,000
|
3
|
25.75
|
25.75
|
8.25
|
15
|
DK132
|
Propane
|
132,000
|
4
|
25.75
|
34
|
8.25
|
17
|
|
|
| IGNITION
TYPE: |
Direct
Spark Ignition
|
| SUPPLY
VOLTAGE: |
115
Volt
|
| AMP
DRAW: |
0.40
Amp
|
| GAS
CONNECTION: |
1/2
" NPT Female
|
|
|
|
|
Model
No. |
Sides |
Ceiling |
Below |
Below
(35º) |
Front
(35º) |
Rear
(35º) |
Angle
Mtg. (degree) |
| Standard
Reflector |
w/Parabolic
Extension |
Standard
Reflector |
w/Parabolic
Extension |
| DK30
DK35
DK33
DK40 |
30" |
36" |
72" |
72" |
100" |
36" |
50" |
30" |
0
min
35 max |
| DK60
DK70
DK66
DK80 |
48" |
48" |
98" |
98" |
137" |
48" |
68" |
36" |
0
min
35 max |
| DK100
DK120 |
48" |
64" |
128" |
128" |
180" |
60" |
84" |
48" |
0
min
35 max |
| DK132
DK160
DK140 |
60" |
64" |
136" |
136" |
190" |
64" |
90" |
48" |
10
min
35 max |
NOTE: The
clearances specified above must be maintained to combustibles and
other materials that may be damaged by temperatures 90ºF above ambient
temperature. Clearances to combustibles are posted on the reflector near
the control end of the heater. In locations used for storage of combustible
materials where they may be stacked below the heater, NFPA 54 requires
that the installer must post signs that will "specify the maximum
permissible stacking height to maintain the required clearances from
the heater to combustibles".
Also, please
note that this heater is NOT for residential use.
|
|
|
| |